				Power Input Range The 
				DPS250AB-44A PSU could operate at wide input voltages defined in 
				below table. 
					
						| 
						Range | 
						Input | 
						Min. | 
						Nom. | 
						Max. |  
						| 
						Low Range | 
						V-in (Wrms) / I-in (Arms) | 
						90 / --- | 
						100-127 / 3.5 | 
						135 / --- |  
						| 
						High Range | 
						V-in (Wrms) / I-in (Arms) | 
						180 / --- | 
						200-240 / 2 | 
						264 / --- |  
						| 
						Frequency (Hz) | 
						47 | 
						--- | 
						63 |  * 
						Inrush current : No component was damaged and input fuse 
						shall not blow. * Input 
				Fuse Requirement : The PSU shall be protected from primary over 
				current by input fuse. * Power 
				factor correction greater than 0.9 at full loading. 
				DC Output Voltage 
				Regulation The DC output 
				voltages of DPS250AB-44A PSU measured at the end of the 
				connectors should be remained within the regulation ranges shown 
				in below table. 
					
						| 
						DC Output | 
						Min. | 
						Nom. | 
						Max. | 
						Tolerance |  
						| 
						+5V (Volts) | 
						+4.75 | 
						+5.00 | 
						+5.25 | 
						+5%, -5% |  
						| 
						+12V (Volts) | 
						+11.4 | 
						+12.00 | 
						+12.60 | 
						+5%, -5% |  
						| 
						-12V 
						(Volts) | 
						-10.8 | 
						-12.00 | 
						-13.20 | 
						+10%, -10% |  
						| 
						+5Vsb 
						(Volts) | 
						+4.75 | 
						+5.00 | 
						+5.25 | 
						+5%, -5% |  
						| 
						+3.3V 
						(Volts) | 
						+3.135 | 
						+3.30 | 
						+3.465 | 
						+5%, -5% |  
						DC Output Load 
						Current Ranges The DC output 
				load current is specified as shown in below table. The maximum 
				continuous output power at steady state operating should be 
				limited at watts. The +5Vsb output should be remained within the 
				regulation limits during the DC fault condition.  
					
						| 
						DC O/P Load | 
						Min. (A) | 
						Nom. (A) | 
						Max. (A) | 
						Peak (A) |  
						| 
						+5V (Volts) | 
						1 | 
						6 | 
						12 |   |  
						| 
						+12V (Volts) | 
						1 | 
						9 | 
						17 | 
						22 |  
						| 
						-12V 
						(Volts) | 
						0 | 
						0.25 | 
						0.5 |   |  
						| 
						+5Vsb 
						(Volts) | 
						0 | 
						1 | 
						2 |   |  
						| 
						+3.3V 
						(Volts) | 
						0 | 
						3 | 
						6 |   |  
						Max. Combined DC 
						Output Max 
				continuous DC output power should not exceed 250W at 25°C 
				and de-rating power 1.6W/°C from 25°C to 50°C to get a maximum 
				continuous power de-rating to 210W at 50°C each output 
				maximum load de-crease in proportion. The total combined 3.3V, 
				5V power should not exceed 60W steady state. The total 
				combined 3.3V, 5V, 12V and -12V power should not exceed 240W. 
				The total peak power should not exceed 300W. The surge 
				duration should be less than 20ms. 
					
						| 
						DC Output | 
						Combined 
						Max. Power | 
						Peak 
						Max. Power |  
						| 
						+3.3V 
						(Volts) | 
						250W | 
						240W | 
						60W | 
						300W |  
						| 
						+5V (Volts) |  
						| 
						+12V (Volts) |       |  
						| 
						-12V 
						(Volts) |  
						| 
						+5Vsb 
						(Volts) |   |  
						Ripple & Noise 
						Specification 
					
						|  | 
						+5V | 
						+12V | 
						-12V | 
						+5Vsb | 
						+3.3V |  
						| 
						Ripple & Noise | 
						50mV | 
						120mV | 
						120mV | 
						50mV | 
						50mV |  (1) 
						Ripple & noise test by the oscilloscope bandwidth are 
						setting at 20MHz. (2) Add a 
				0.1µF ceramic disk capacitor in parallel with a 10µF 
				electrolytic capacitor at output connector terminals for ripple 
				& noise measurements. If ambient temperature is under 20°C or 
				over 30°C, the AC input should be nominal input. 
				Efficiency The 
				efficiency of the power supply during normal operating should be 
				in below table at 115Vac/230Vac line input voltage.  
					
						| 
						Efficiency | 
						+12V | 
						+5V | 
						+3.3V | 
						-12V | 
						+5Vsb | 
						% of Full Load |  
						| 
						> 82% | 
						3.04A | 
						1.61A | 
						0.81A | 
						0.09A | 
						0.36A | 
						20%  |  
						| 
						> 85% | 
						7.59A | 
						4.03A | 
						2.01A | 
						0.22A | 
						0.89A | 
						50% |  
						| 
						> 82% | 
						15.18A | 
						8.06A | 
						4.03A | 
						0.446A | 
						1.786A | 
						100% |  
						Standby Efficiency At 115Vac, 
				while in standby mode with a 100mA load on the +5Vsb DC output, 
				the PSU should draw less than 1 watt of true input power. 
				 
				Over Voltage Protection +5V, +3.3V 
				and +12V output of PSU should be protected from over voltage as 
				below table..  
					
						| 
						DC Output | 
						+12V | 
						+5V | 
						+3.3V |  
						| 
						Max. | 
						15.6V | 
						7V | 
						4.8V |  
						Environmental 
						Requirement Operating 
				Temperature : 0 to 50°C. Storage 
				Temperature : -40 to 70°C. Operating 
				Humidity : 20 to 85% related humidity (non-condensing). Non-Operating 
				Humidity : 10 to 95% related humidity (non-condensing). 
				Electromagnetic 
				Compatibility and Safety Requirements Conducted EMI 
				: CE, BSMI, FCC, CISPR 22 class B. Safety : 
				UL+CUL, TUV EN60950-1, CB, CCC, CE, BSMI. 
				Reliability MTBF : > 
				100,000 hours under 100% loading / 25°C. 
				Dimension Body : 81.5 x 
				40.5 x 150 mm (W x H x D) |